Quick Start Guide
15
January 2015
I6 CSA Intrinsically Safe and Division 2
Certificate: 1261865
Standards: CAN/CSA C22.2 No. 0-M91 (R2001), CAN/CSA C22.2 No. 94-M91,
CSA Std. C22.2 No. 142-M1987, CSA Std. C22.2 No. 157-92,
CSA Std. C22.2 No. 213-M1987, CSA Std. C22.2 No. 60529:05
Markings: Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D;
T3C(-50 °C
≤ T
a
≤ +60 °C) when installed per Rosemount drawing
00848-4405; Class I, Division 2, Groups A, B, C, D;
T3C(-50 °C ≤ T
a
≤ +60 °C) when installed per Rosemount drawing
00848-4405
IF CSA FISCO
Certificate: 1261865
Standards: CAN/CSA C22.2 No. 0-M91 (R2001), CAN/CSA C22.2 No. 94-M91,
CSA Std. C22.2 No. 142-M1987, CSA Std. C22.2 No. 157-92,
CSA Std. C22.2 No. 213-M1987, CSA Std. C22.2 No. 60529:05
Markings: Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D;
T3C(-50 °C
≤ T
a
≤ +60 °C) when installed per Rosemount drawing
00848-4405; Class I, Division 2, Groups A, B, C, D;
T3C(-50 °C ≤ T
a
≤ +60 °C) when installed per Rosemount drawing
00848-4405
N6 CSA Division 2 and Dust-Ignitionproof (enclosure required)
Certificate: 1261865
Standards: CAN/CSA C22.2 No. 0-M91 (R2001), CSA Std. C22.2 No. 30-M1986,
CAN/CSA C22.2 No. 94-M91, CSA Std. C22.2 No. 142-M1987,
CSA Std. C22.2 No. 213-M1987, CSA Std. C22.2 No. 60529:05
Markings: Class I, Division 2, Groups A, B, C, and D; T3C(-50 °C
≤ T
a
≤ +60 °C) when
installed per Rosemount drawing 00848-4405; Dust-Ignitionproof for
Class II, Division 1, Groups E, F, and G; Class III; Conduit Seal Required
Europe
I1 ATEX Intrinsic Safety
Certificate: Baseefa09ATEX0093X
Standards: EN 60079-0:2012, EN60079-11:2012
Markings: II 1 G Ex ia IIC T4 Ga (-50 °C
≤ T
a
≤ +60 °C) when installed per drawing
00848-4406
Special Conditions for Safe Use (X):
1. The equipment must be installed in an enclosure that provides a degree of
protection of at least IP20. Non-metallic enclosures must be suitable to
prevent electrostatic hazards and light alloy or zirconium enclosures must be
protected from impact and friction when installed.
2. The equipment is note capable of withstanding the 500 V insulation test
required by EN 60079-11:2012, clause 6.3.13. This must be taken into
account when installing the equipment.