Reference Manual
00809-0200-4420, Rev HB
Section 3: Mounting and Connection
January 2015
Mounting and Connection
Figure 3-6. Terminal Block Diagram
Ethernet connections should use Cat5E shielded cable to connect to an Ethernet hub, switch, or
router. The maximum cable length should not exceed 328 ft. (100 m).
Note
Unless dual Ethernet ports were specified at the time of order, the secondary Ethernet port
(Ethernet 2) will not be active.
3.4.3 RS-485
The Gateway may be ordered with an optional RS-485 (serial) connection (Figure 3-6). It is
referenced by the A and B Serial Modbus terminals. This connection is used to communicate
Modbus RTU on an RS-485 data bus.
Use 18 AWG single twisted shielded pair wiring to connect the Gateway to the RS-485 data bus.
The total bus length should not exceed 4000 ft. (1220 m). Connect the Tx + (positive, transmit)
wire to terminal A and the Rx - (negative, receive) wire to terminal B. The wiring shield should be
trimmed close and insulated from touching the Gateway enclosure or other terminations.
If the existing data bus uses a 4 wire Full Duplex configuration, see Figure 3-7 to convert to a
2-wire Half Duplex configuration.
Figure 3-7. Convert from Full to Half Duplex
+
+
+
+
+
-
-
-
-
-
AB
S
S
S
S
24 VDC
(nominal)
Power Input
Serial
Modbus
Not
Us
e
d
Not
Us
e
d
N
ot
Us
e
d
Not
Us
e
d
Case
(Covered)
S
Ethernet 2
with Power
Ethernet 2
Ethernet 1
(Secondary) (Primary)
Tx
Rx
T
x
Rx
(A)
(B)