Host Integration
5.5 Ethernet/IP
Communication settings
It is important that the Ethernet/IP communication settings in the Gateway match the setting in
the Ethernet/IP master or client. Please refer to host system documentation for more
information on how to configure these settings. Or to the reference manual for Ethernet/IP
technical document 00809-0500-4420. The Ethernet/IP communication settings can be found
by navigating to System Settings>Protocols>EtherNet/IP. Network architectures should reflect
that of a DeltaV
system see 00809-0200-4420, Rev HB.
Note
Ethernet/IP can be integrated with any approved Ethernet/IP ODVA member. Other protocols
such as HARTIP are still functional within the Gateway. See the Product Data Sheet (document
number 00813-0200-4420) for ordering options.
SYSTEM_DIAG.ADDITIONAL_STATUS_4 49019 8-bit unsigned int
SYSTEM_DIAG.ADDITIONAL_STATUS_5 49020 8-bit unsigned int
SYSTEM_DIAG.ADDITIONAL_STATUS_6 49021 8-bit unsigned int
SYSTEM_DIAG.ADDITIONAL_STATUS_7 49022 8-bit unsigned int
SYSTEM_DIAG.ADDITIONAL_STATUS_8 49023 8-bit unsigned int
SYSTEM_DIAG.ADDITIONAL_STATUS_9 49024 8-bit unsigned int
SYSTEM_DIAG.ADDITIONAL_STATUS_10 49025 8-bit unsigned int
SYSTEM_DIAG.ADDITIONAL_STATUS_11 49026 8-bit unsigned int
SYSTEM_DIAG.ADDITIONAL_STATUS_12 49027 8-bit unsigned int
SYSTEM_DIAG.UNREACHABLE 49028 32-bit int
SYSTEM_DIAG.UPTIME 49029 32-bit int
SYSTEM_DIAG.TEST_BOOLEAN 49031 Boolean
SYSTEM_DIAG.TEST_BYTE 49032 8-bit int
SYSTEM_DIAG.TEST_UNSIGNED_BYTE 49033 8-bit unsigned int
SYSTEM_DIAG.TEST_SHORT 49034 16-bit int
SYSTEM_DIAG.TEST_UNSIGNED_SHORT 49035 16-bit unsigned int
SYSTEM_DIAG.TEST_INT 49036 32-bit int
SYSTEM_DIAG.TEST_UNSIGNED_INT 49038 32-bit unsigned int
SYSTEM_DIAG.TEST_FLOAT 49040 32-bit float
Table 5-2. Predefined Modbus Registers